Home > Products > Power Cable > RVV Power Cord

RVV Power Cord

As the professional manufacture, we would like to provide you RVV Power Cord. And we will offer you the best after-sale service and timely delivery.

Send Inquiry

Product Description

Cross Section


Environment

Operating temperature range (℃) 

-40~70

Min. installation temperature(℃)

-10

Storage temperature range (℃)

-40~50


RVV Power Cord Color

Number of cores

Priority Color

Insulation

2 cores

no priority

3 cores

yellow/green、 brown、 blue

4 cores

yellow/green、 brown、 blac、gray

5 cores

yellow/green、 blue、brown、 black、gray

6 cores

yellow/green、 blue、brown、 black、gray、red

Oversheath

Black


Electrical Characteristics

Conductor resistance (Ω/km)

Insulation resistance constant

See table paramenter of products

Voltage test on cores (1.5kV, 5min, Specified value of thickness ≤.6mm)

No breakdown

Voltage test on cores (2.0kV, 5min, Specified value of thickness >0.6mm) No breakdown


Mechanical and Physical Characteristics

1.Conductor

Conductor

Nominal diameter (mm)

Elongation at rupture(%)

0.100<d≤0.300

≥15

0.300<d≤0.600

>20


2.Insulation

Before aging

Tensile strength (M/Pa)

≥10.0

Elongation at rupture(%)

≥150

Aging condition

100℃±2℃, 168h

After aging

Tensile strength (M/Pa)

≥10.0

Variation of tensile strength(%)

≤±20

日ongation at rupture(%)

≥150

Variation of elongation at rupture(%)

±20

Pressure test at high temperature (80℃±2℃,4h)

≤50%

Bending test at low temperature (-40℃±2℃,4h)

No crack

Heat shock test (150℃±3℃,1 h)

No crack

Loss of mass test (80t℃±2℃,168h) (mg/cm2)

≤2.0


3.Jacket

Before aging

Tensile strength (M/Pa)

≥10.0

日ongation at rupture(%)

≥150

Aging condition

100℃±2℃, 168h

After aging

Tensile strength (M/Pa)

≥10.0

Variation of tensile strength(%)

≤±20

Elongation at rupture(%)

≥150

Variation of elongation at rupture(%)

≤±20

Pressure test at high temperature (80℃±2℃,4h)

≤50%

Bending test at low temperature (-40℃±2℃,4h)

No crack

Heat shock test (150℃±3℃,1 h)

No crack

Loss of mass test (80℃±2℃,168h) (mg/cm2)

≤2.0


4.Test on Completed Cable

Impact test at low temperature (-40℃~2℃): No crack


Marking

KINGSIGNAL RVVP 300/300V n*Xmm2 YYWW ****M

Remark: Here, "n" is the core's number and "X" is the cross-sectional area. 'YYWW' is year and month.


Environment Requirements

RoHS & REACH: Compliant


Number of cores

Nominal cross-sectional area

Conductor structure

Conductor diameter (Nom.)

Max. conductor DC resistance at 20℃

Min. insulation  resistance at 70℃

Nominal insulation thickness

Insulation Diameter(No m.)

Diameter of wires in Shied

Nominal oversheath thickness

Jacket diameter (Nom.)

(mn)

(±0.004mm)

(mm)

(Ω/km)

(MΩ/km)

(mm)

(mm)

(mm)

(mm)

(mm)

2

1.5

27/0.25

1.52

13.3

0.010

0.6

3.00

0.15

0.8

8.20

2.5

46/0.25

1.96

7.98

0.009

0.7

3.70

0.16

1.0

10.04

4

56/0.287

2.48

4.95

0.007

0.8

4.20

0.21

1.0

11.24

6

84/0.287

3.17

3.30

0.006

0.8

3.7*5.7

0.21

1.1

10.44

6

84/0.287

3.17

3.30

0.006

0.8

4.70

0.21

1.1

12.44

3

1.0

34/0.19

1.28

19.5

0.010

0.6

2.48

0.15

0.8

7.54

1.5

27/0.25

0.26

13.3

0.010

0.6

3.00

0.15

0.8

8.67

2.5

46/0.25

0.26

7.98

0.009

0.7

3.70

0.16

1.0

10.61

4

56/0.287

2.48

4.95

0.007

0.8

4.20

0.21

1.2

12.29

6

84/0.287

3.17

3.30

0.006

0.8

4.70

0.21

1.2

13.37

10

75/0.40

4.00

1.91

0.0056

1.0

6.20

0.21

1.4

17.00

4

0.75

26/0.19

1.12

26.0

0.010

0.5

2.22

0.16

0.8

7.60

1.0

34/0.19

1.28

19.5

0.010

0.6

2.48

0.16

0.9

8.43

1.5

27/0.25

0.26

13.3

0.010

0.6

3.00

0.16

0.9

9.68

2.5

46/0.25

0.26

7.98

0.009

0.7

3.70

0.16

1.0

11.57

4

56/0.287

2.48

4.95

0.007

0.8

4.20

0.16

1.2

13.18

5

0.5

26/0.15

0.88

39.0

0.013

0.5

1.95

0.16

0.8

7.49

0.75

26/0.19

1.12

26.0

0.010

0.5

2.22

0.16

0.8

8.22

1.0

34/0.19

1.28

19.5

0.010

0.6

2.48

0.16

0.9

9.12

1.5

27/0.25

0.26

13.3

0.010

0.6

3.00

0.16

1.0

10.72

2.5

46/0.25

0.26

7.98

0.009

0.7

3.70

0.21

1.1

13.00

4

56/0.287

2.48

4.95

0.007

0.8

4.20

0.21

1.4

14.95

6

0.5

26/0.15

0.88

39.0

0.013

0.5

1.95

0.16

0.8

7.76

0.75

26/0.19

1.12

26.0

0.010

0.5

2.22

0.16

0.8

8.52

1.0

34/0.19

1.28

19.5

0.010

0.6

2.48

0.16

1.0

9.65

1.5

27/0.25

0.26

13.3

0.010

0.6

3.00

0.16

1.0

11.12

2.5

46/0.25

0.26

7.98

0.009

0.7

3.70

0.21

1.1

13.50



Hot Tags: RVV Power Cord, Manufacturers, Suppliers, Factory, Wholesale, China, Made in China, Price, 3C/UL, Customized